Overview
In order for Altrac's Pump Station to control pump equipment, you will need to install the Pump Buddy and make connections between the Pump Buddy and the VFD or Contactor Setups. The goal of installing the Pump Buddy is to contain all high voltage currents inside the pump cabinet, so that a non-electrician can install the Altrac Station and troubleshoot the low voltage circuits (pressure transducers, etc.).
Pump Buddy
The Pump Buddy comes with 2 M12 Connectors for use with the Altrac Station. You must install conduit between the pump cabinet(s) and the pump buddy and run appropriate cable. See below for an example:
The pump buddy should be installed close to the pump cabinet in a location we can mount the Altrac Station (similar size to the pump buddy). The Altrac Station is normally mounted like the image below:
Equipment
You should have the following equipment on hand for installs. The equipment is also highlighted in blue on the schematics:
- Power Supply
- Must output 15VDC (30W minimum)
- Pump Station Power Consumption: 2A peak usage
- Step Up Relay
- 15VDC Coil Voltage -> Control Voltage
- Selector Switch Contact Block
- To monitor HOA switch position, you may need to install an additional contact block (shown below)
Schematics
Contactor or 120VAC Control Voltage Setups
Anything in blue, you must provide during installation.
VFD
Anything in blue, you must provide during installation.
Testing - Pump Control
You must test each contact for proper function.
Location | Use | Test |
Pin 1 | 15VDC Power | 15 VDC power present |
Pin 2 | GND | Continuity Pin 2 -> GND Power Supply |
Pin 3 | RS485A | N/A |
Pin 4 | RS485B | N/A |
Pin 5 | RS485 GND | N/A |
Pin 6 and 7 | Relay A, Relay B |
|
Pin 8 | HOA A |
|
Testing - Pump Monitoring Only
You must test each contact for proper function. This setup is for installation where the grower is monitoring pressure or flow meters. This is NOT for pump control.
Location | Use | Test |
Pin 1 | 15VDC Power | 15 VDC power present |
Pin 2 | GND | Continuity Pin 2 -> GND Power Supply |
Pin 3 | RS485A | N/A |
Pin 4 | RS485B | N/A |
Pin 5 | RS485 GND | N/A |
Pin 6 and 7 | Relay A, Relay B |
N/A |
Pin 8 | HOA A | N/A |
Pump 1: M12 Connector
Location |
Use |
Altrac Input |
Color |
Notes |
---|---|---|---|---|
Pin 1 |
Power |
Power - VIN |
White |
15VDC |
Pin 2 |
Ground |
Power - GND |
Brown |
GND |
Pin 3 |
RS485A |
RS485/RS232 A / TX |
Green |
|
Pin 4 |
RS485B |
RS485/RS232 B / RX |
Yellow |
|
Pin 5 |
RS485 GND |
RS485 GND |
Gray |
|
Pin 6 |
Relay 1 A |
Relay 1 - NO |
Pink |
Normally Open |
Pin 7 |
Relay 1 B |
Relay 1 - COM |
Blue |
15VDC |
Pin 8 |
HOA A |
Digital Input 1 DIN1 |
Red |
15VDC |
Pump 2: M12 Connector
Location |
Use |
Altrac Input |
Color |
Notes |
---|---|---|---|---|
Pin 1 |
Power |
Power - VIN |
White |
15VDC |
Pin 2 |
Ground |
Power - GND |
Brown |
GND |
Pin 3 |
RS485A |
RS485/RS232 A / TX |
Green |
|
Pin 4 |
RS485B |
RS485/RS232 B / RX |
Yellow |
|
Pin 5 |
RS485 GND |
RS485 GND |
Gray |
|
Pin 6 |
Relay 2 A |
Relay 2 - NO |
Pink |
Normally Open |
Pin 7 |
Relay 2 B |
Relay 2 - COM |
Blue |
15VDC |
Pin 8 |
HOA A |
Digital Input 2 DIN2 |
Red |
15VDC |
HOA Switch
The ST140 detects the position of the HOA switch in order to tell users when the pump is in Auto mode and the ST140 can control the pump.
WARNING: Use an empty terminal block on the HOA switch to provide the signal to the ST140. If you wire the HOA detection into an in-use terminal you will mix electrical signals and receive unpredictable results.
1) Determine if the HOA switch has a free terminal block for Auto-detection. In an existing installation, the HOA switch will have wires connected to both its Hand and Auto terminals used to turn the pump on and off in both Hand and Auto modes.
IMPORTANT: If there are no free terminals, you will need to add a stacking contact block to the auto side of the HOA switch. Do not wire into a used contact block.
2) Follow connections diagram “HOA.1” below to wire the ST140 Digital Input to detect the Auto position
ST140 DIN1 Terminal connect to HOA Auto NO
ST140 GND Terminal connect to HOA Auto COM
Controlling the VFD - No HOA Switch
Fuji Frenic Eco
The ST140 sends a control signal via its mechanical relays, Relay 1 and Relay 2. The contacts COM/NO/NC are “dry” and so act similarly to a Hand-Off-Auto switch.
1) The Inverter must be set to accept run and stop commands via its control circuit terminal FWD. If you have a Hand-Off-Auto switch currently in place controlling your Inverter, it’s likely the inverter is set up correctly. To double-check, go to function code F02 and ensure it is set to “1: Digital Input”. If this is not how the Inverter is set up, you will need to modify the inverter for this control method; for more detail see Frenic Eco manual pages 3-42 and 8-11.
2) Determine if the Inverter’s control circuit is set to SINK mode (default) or SOURCE mode. See diagram “Frenic.1” below.
3) Follow connections diagram “Frenic.2” below to wire the ST140 relay to control the Inverter
ST140 Relay X Terminal - COM:
SINK mode: connect to Inverter CM terminal
SOURCE mode: connect to Inverter PLC terminal
ST140 Relay X Terminal - NO:
BOTH modes: connect to Inverter FWD terminal
Allen Bradley PowerFlex
The ST140 sends a control signal via its mechanical relays, Relay 1 and Relay 2. The contacts COM/NO/NC are “dry” and so act similarly to a Hand-Off-Auto switch.
1) The Inverter must be wired for “2-Wire” control, the default for this Inverter. If you have a Hand-Off-Auto switch currently in place controlling your Inverter, it’s likely the inverter is set up correctly. If this is not the case, refer to the Installation manual for a proper 2-Wire control setup.
2) Follow the connections diagram “PowerFlex.1” below to wire the ST140 relay to control the Inverter. Depending on your Inverter setup, you may use different terminals from PowerFlex +24V and PowerFlex Di 1
Comments
0 comments
Please sign in to leave a comment.